Product Description
6
Figure 9 Piping access points
Table 2 Unit piping outlet connection sizes, inches, OD Cu
Model Pipe Connection Point
50/60 HzABCD
XDP160 2-1/8 1-1/8 2-5/8 2-5/8
Dimensions are
approximate
and subject to change
without notice.
16-1/8"
(410mm)
17-1/4"
(438mm)
10" (254mm)
19"
(483mm)
A - Return From Cooling Modules
B - Supply to Cooling Modules
D - Chilled Water Return
To Chilled Water Source
C - Chilled Water Supply
From Chilled Water Source
* Allow 8" (204mm) clearance for filter replacement.
** To ensure ensure all refrigerant flow is filtered, install the filter dryer assembly
between the discharge line of the Liebert XDP and the first bypass flow controller
or the first cooling module.
DPN000767
Pg. 3, Rev. 6
Install replaceable filter dryer assembly
in liquid supply line B.
To first cooling module
or bypass flow controller **
* Orientation
determined
by installer.